Commissioning
Prosonic S FMU95
52
E Hauser
!
Hinweis!
In order to optimeze the cycle time of the measured value update, it is recommended to deactivate
unused measuring channels in the "sensor management" menu
67.
Step
Parameter Set
Parameter
Remarks
page
Interference echo suppression
7
lvl N check value
(N = 1 - 10)
act. distance N
(N = 1 - 10)
Indicates the currently measured distance between the sensor membrane
and the product surface.
check distance
Compare the indicated distance with the real value:
• "distance = ok"
"distance mapping" (see below)
• "distance too small"
"distance mapping" (see below)
• "distance too big"
Basic setup completed
• "distance unknown"
Basic setup completed
• "manual"
"distance mapping" (see below)
8
LVL N dist. map.
(N = 1 - 10)
act. distance N
(N = 1 - 10)
Indicates the currently measured distance between the sensor membrane
and the product surface.
range of mapping
Determines the range over which the mapping is recorded;
confirm the predefined value or enter your own value.
start mapping
Select:
• no: the mapping is not recorded
• yes: the mapping is recorded; after completion the "LVL N state" function
appears (see below)
9
LVL N state
(N = 1 - 10)
level N
(N = 1 - 10)
Indicates the currently measured level.
act. distance
Indicates the currently measured distance between the sensor membrane
and the product surface. Check the value:
• Value correct:
Basic setup completed.
Return to the measured value display by pressing
several times
• Value not incorrect:
go back to step 7 ("distance correction")
status
Used to enable, disable or delete a mapping