Wiring
Prosonic S FMU95
18
E Hauser
4.2
Terminal assignment
L00-FMU90xxx-04-00-00-xx-001
Terminals of the Prosonic S FMU95; the terminals depicted in grey are not present in every instrument version.
Address
T
erm.
DP
of
f
on
of
f
on
SW
HW
1
2
3
4
5
6
7
8
1
2
3
4
A(N)
66
B(P)
65
Display
POWER
Sync
Fuse
40
39
Service
3
2
1
11
10
9
1
FDU-Sensor
YE
BK
RD
14
13
12
2
YE
BK
RD
17
16
15
3
YE
BK
RD
20
19
18
4
YE
BK
RD
23
22
21
5
YE
BK
RD
26
25
24
6
YE
BK
RD
29
28
27
7
YE
BK
RD
32
31
30
8
YE
BK
RD
35
34
33
9
YE
BK
RD
38
37
36
10
YE
BK
RD
FDU-Sensor
Terminals
Meaning
Remarks
Auxiliary energy
1
• L (for AC version)
• L+ (for DC version)
depending on instrument version:
• 90 ... 253 V
AC
• 10,5 ... 32 V
DC
2
• N (for AC version)
• L- (for DC version)
3
Potential equalization
Fuse
depending on instrument version:
• 400 mA T (for AC)
• 2 A T (for DC)
Bus communication
65
PROFIBUS A (RxT/TxD - N)
66
PROFIBUS B (RxT/TxD - P)
Synchronization
39, 40
Synchronization
Level inputs
09,10,11
Sensor 1 (FDU8x/9x)
YE: yellow strand
BK: black strand
RD: red strand
12, 13, 14
Sensor 2 (FDU8x/9x)
15, 16, 17
Sensor 3 (FDU8x/9x)
18, 19, 20
Sensor 4 (FDU8x/9x)
21, 22, 23
Sensor 5 (FDU8x/9x)
24, 25, 26
Sensor 6 (FDU8x/9x)
only available for the version with 10 sensor inputs
YE: yellow strand
BK: black strand
RD: red strand
27, 28, 29
Sensor 7 (FDU8x/9x)
30, 31, 32
Sensor 8 (FDU8x/9x)
33, 34, 35
Sensor 9 (FDU8x/9x)
36, 37, 38
Sensor 10 (FDU8x/9x)