Prosonic S FMU95
Commissioning
E Hauser
55
"process conditions"
Use this parameter to specify the process conditions of your application. The filters of the signal
evaluation are automatically adjusted to the selected conditions.
"process conditions"
for the following situations
Example
filter settings
standard liquid
for all fluid applications which do
not fit in any of the following
groups
The filters and output damping are set
to average values.
calm surface
Storage tanks with immersion
tube or bottom filling
The averaging filters and output
damping are set to large values.
-> stable measured value
-> accurate measurement
-> slow reaction time
turbulent surface
Storage/accumulation tanks with
uneven surface due to free filling,
mixing nozzles or small bottom
stirrers
Special filters for stabilizing the input
signal are activated.
-> stable measured value
-> medium reaction time
additional agitator
Moving surfaces (possibly with
vortex formation) due to agitators
Special filters for stabilizing the input
signal are set to large values.
-> stable measured value
-> medium reaction time
fast change
Rapid level change, particularly in
small tanks
The averaging filters are set to small
values.
-> rapid reaction time
-> possibly unstable measured value
standard solid
For all bulk solid applications
which do not fit in any of the
following groups.
The filter and output damping are set
to average values.
solid dusty
Dusty bulk solids
The averaging filters are set to detect
even relatively weak signals.
conveyor belt
Bulk solids with rapid level change
The averaging filters are set to small
values.
-> rapid reaction time
-> possibly unstable measured value
test: no filter
For service and diagnosis only
All filters are switched off