Prosonic S FMU95
Commissioning
E Hauser
45
Hardware addressing
L00-FMU90xxx-04-00-00-xx-016
Hardware addressing comes into operation when DIP switch 8 is in the position "HW (OFF)". In this
case the address is determinded by the position of DIP-switches 1 to 7 according to the following
table:
The new address becomes valid 10 seconds after switching.
6.1.2
Bus termination
The termination resistor must be activated for the last instrument on the bus. This is done by setting
all four termination switches into the "on" position.
L00-FMU90xxx-04-00-00-xx-018
A: termination off (factory setting); B: termination on