Commissioning
Prosonic S FMU95
66
E Hauser
The Prosonic S changes to the
"distance mapping"
parameter set, where you can define the
required range of mapping.
"LVL N distance mapping" (N = 1 - 10)
"actual distance N" (N = 1 - 10)
Displays the currently measured distance between the sensor membrane (reference point of the
measurement) and the product surface. Compare this value to the real distance in order to find out
if currently an interference echo is evaluated.
"range of mapping"
Use this parameter to specify the range of the mapping curve. Normally, a suitable value has already
been entered automatically. Nevertheless, you can change this value if required.
"start mapping"
Select
"yes"
in this parameter in order to start the mapping. When the mapping is finished, the state
is automatically changed to
"enable map"
.
The
"LVL N state"
parameter set appears, in which the currently mesaured level and distance are
displayed. Compare the displayed distance to the real distance in order to decide if a further mapping
is necessary.
If yes: Press the left-arrow key (
) in order to return to the
"LVL N dist. map"
parameter set.
If no: Press the right-arrow key (
), in order to return to the
"level (LVL) N"
submenu.
LVL1 dist.map.
L100B
act. distance 1:
range of mapping:
start mapping:
status: