Commissioning
Prosonic S FMU95
48
E Hauser
Hardware locking
The instrument can be locked against parameter changes by the locking switch in the terminal
compartment of the Prosonic S.
L00-FMU90xxx-19-00-00-yy-105
Switch position A: unlocked; parameters can be changed
Switch position B: locked; parameters can not be changed.
If the switch is in position B,
appears on the display and parameters can not be changed. The
instrument can only be unlocked by the switch.
6.1.5
Reset to the default configuration
"
Caution!
A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after
a reset.
Application of the Reset
It is advisable to reset the customer parameters if you want to use a device with an unknown history.
Effects of the Reset
• All parameters are reset to their default values.
• The linearisation type is switched to "none". If a linearisation table is present, it is not deleted. If
required, it can be reactivated at a later point of time.
• An interference echo curve is set "inactive". However, the curve is not deleted and can be
reactivated at a later point of time.
!
Note!
In the menu diagrams (
96, "Operating menu") the default values of the parameters are printed
in bold.
Performing a Reset
In order to perform a reset, enter "33333" into the parameter "device properties/password-reset/
reset".
Display
POWER
Sync
Fuse
4
0
39
Service
3
2
1
A
B