Commissioning
Prosonic S FMU95
56
E Hauser
"LVL N empty calibration" (N = 1 - 10)
"empty E"
LVL1 empty cal.
L1005
empty E:
0,00 m
L00-FMU90xxx-19-00-00-yy-007
Use this parameter to specify the empty distance E, i.e. the
distance between the sensor membrane (reference point of the
measurement) and the minimum level (zero point).
– Default: max. measuring range of the respective sensor
– Range of values: depending on sensor type
"
Caution!
The zero point should not be deeper than the point at which the
ultrasonic wave impinges on the tank bottom
0/4 mA
0%
E