Instruction Manual
IM-106-910C, Rev. 1.0
November 2009
2-17
Hazardous Area
X-STREAM O
2
Transmitter
Optional Flame Safety
Interlock
A flame safety interlock by Emerson Process Management is available for
heater power disconnect whenever there is a loss of the process flame or a
heater runaway condition (heater over-temperature) in the X-STREAM O
2
Transmitter. A simplified wiring diagram for the flame safety interlock is shown
in Figure 2-15. This input is internally powered by the Xi Enhanced Interface
and is actuated via a dry contact output from the user’s flame scanner. A
closed contact indicates a flame is present. An open contact indicates a loss
of flame.
Figure 2-15. Flame Safety Interlock - Wiring Diagram
Traditional Architecture
Cable Connections
A traditional architecture X-STREAM O
2
Transmitter configuration is used to
provide for remote location of the transmitter electronics. All electronics are
housed inside the Xi Enhanced Interface. A multi-conductor power/signal
cable connects between the probe and the Xi. Use the following procedure to
connect the traditional architecture probe to the Xi Enhanced Interface.
NOTE
The Traditional Architecture cable is provided at the specified length and is
ready for installation. The cable glands must be properly terminated to
maintain EMC/EMI noise protection.
Содержание Rosemount X-STREAM O2 Transmitter
Страница 2: ......
Страница 4: ......
Страница 8: ...Hazardous Area X STREAM O2 Transmitter TOC 4 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 10: ...Hazardous Area X STREAM O2 Transmitter ii Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 32: ...Hazardous Area X STREAM O2 Transmitter 1 16 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 58: ...Hazardous Area X STREAM O2 Transmitter 2 26 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 66: ...Hazardous Area X STREAM O2 Transmitter 3 8 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...