Hazardous Area
X-STREAM O
2
Transmitter
Figure 2-1. Typical System
Installation
If the calibration gas bottles will be permanently connected a check valve is
required next to the calibration fittings on the probe. This check valve is to
prevent breathing of the calibration gas line and subsequent flue gas
condensation and corrosion. The check valve is in addition to the stop valve
on the calibration gas bottles or the solenoid valves in the SPS 4001B or
IMPS 4000.
If the Xi Enhanced Interface option is not used, the 4 to 20 mA signal from the
probe will be loop-powered from the DCS. A 375 Field Communicator or AMS
is required to set up and operate the probe.
The optional Xi Enhanced Interface communicates with the probe transmitter
electronics via HART communications riding on the 4 to 20 mA signal coming
from the transmitter. If using the 375 Field Communicator, it must be
connected to the 4 to 20 mA signal loop between the Xi and the control room
or data acquisition system. Connecting the 375 Field Communicator between
the transmitter and Xi will cause communication errors and affect system
operation.
NOTES:
The transmitter electronics is rated Type 4X and IP66 and is capable of
operation at temperatures from -40 to 85°C (-40 to 185°F).
Retain the packaging in which the X-STREAM arrived from the factory in case
any components are to be shipped to another site. This packaging has been
designed to protect the product.
Содержание Rosemount X-STREAM O2 Transmitter
Страница 2: ......
Страница 4: ......
Страница 8: ...Hazardous Area X STREAM O2 Transmitter TOC 4 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 10: ...Hazardous Area X STREAM O2 Transmitter ii Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 32: ...Hazardous Area X STREAM O2 Transmitter 1 16 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 58: ...Hazardous Area X STREAM O2 Transmitter 2 26 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 66: ...Hazardous Area X STREAM O2 Transmitter 3 8 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...