Hazardous Area
X-STREAM O
2
Transmitter
2-16
Instruction Manual
IM-106-910C, Rev. 1.0
November 2009
4. Terminate the shield of the 4-20 mA signal wires at the designated
ground terminal of the Xi Enhanced Interface. Do not allow bare shield
wires to contact the circuit boards. Insulate the shield wires prior to
termination.
5. Connect the signal wires from the SPS or IMPS (if used) to the
applicable terminals of J3. Refer to the SPS or IMPS instruction manual
for wiring details.
6. Connect the signal wires for the flame status input (if used) to the
applicable terminals of J2. The flame status sensing device is supplied
by the customer. Refer to the applicable OEM documents for signal
wiring details.
7. Connect the customer’s alarm indicator devices to the alarm indicator
relay terminals. See Figure 2-13 for the alarm indicator relay terminals.
8. Reinstall the I/O board in the card rack of the Xi Enhanced Interface.
9. If your system is configured to operate two transmitter probes, repeat
steps 2 through 7 to connect the other probe signal wires.
10. Remove the connector from the power supply board located on the
left-hand side of the card rack inside the Xi Enhanced Interface.
11. See Figure 2-14. Connect the line, or L1 wire to the L1 terminal and the
neutral, or L2 wire, to the N terminal.
12. Reinstall the power supply connector in the power supply board.
13. Close and fasten the cover of the Xi Enhanced Interface.
Figure 2-14. Power Connections - Xi Enhanced Interface
Содержание Rosemount X-STREAM O2 Transmitter
Страница 2: ......
Страница 4: ......
Страница 8: ...Hazardous Area X STREAM O2 Transmitter TOC 4 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 10: ...Hazardous Area X STREAM O2 Transmitter ii Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 32: ...Hazardous Area X STREAM O2 Transmitter 1 16 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 58: ...Hazardous Area X STREAM O2 Transmitter 2 26 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...
Страница 66: ...Hazardous Area X STREAM O2 Transmitter 3 8 Instruction Manual IM 106 910C Rev 1 0 November 2009 ...