Installation Instructions
Read the following instructions
carefully before installing the unit.
Thank you for choosing a EMBRACO Sliding unit. It is housed air cooled condensing unit. This unit has been
specifically designed for refrigeration and with service friendly installation in mind to save your time on
site: easy access to components.
This technical instruction leaflet includes detailed information concerning installation, start up, servicing
and maintenance.
1. WARNING
1.1 Transport and handling.
Do not transport or handle the unit up-side down because the unit contains
compressor with oil.
1.2 Installation.
• This condensing unit and all related equipment must be installed by qualified staff.
• The installation should be carried out in accordance with the relevant refrigeration and electrical
standards which apply in that country. Refrigeration best practice must be followed.
• EMBRACO shall not under any circumstance be liable if the installation and maintenance are not carried
out in accordance with the instructions given in this manual.
2. TECHNICAL DATA
2.1 Identification label for the HOUSED CONDENSING UNIT range
(See picture
1
)
Always check if the
label correspond to the required model to be installed.
2.2 Safety devices.
All units are supplied with an adjustable LP pressure switch and fixed value HP
pressure switch, with a 6A maximum current rating.
3. INSTALLATION
3.1 Unpacking.
Before unpacking the unit, check that the packaging has not been damaged in any way
and that the exterior is in good condition.
3.2 Handling.
The packaged condensing unit can be lifted by forklift or pallet truck The unit should
therefore be kept in its packaging until it has been moved to the installation site. Once the packaging has
been removed, “sliding units” can be moved.
Warning:
do not lift or move the product by its housing when opening the housing.
3.3 Location.
Housed condensing units should not block or obstruct thoroughfares, doors, shutters or the
movement of personnel. The surface supporting the condensing unit must be level and capable of bearing the
combined weight of the unit + support. Ensure there is sufficient distance between the condensing unit and
objects in the surrounding area to ensure good air circulation.
MIN: 200 mm free area.
(See picture
2
)
Housed condensing units must be installed in well ventilated but not windy locations. Ensure there is
good air circulation to the condenser. There must be no obstacles in front or to the side of the unit which
would cause air recirculation to the condenser resulting in an abnormally high condensation temperature.
The housed condensing unit must be mounted in a level position according to best refrigeration practice.
Ensure that the condensing unit is kept away from heat sources, damp areas, corrosive atmospheres or
any sites where there is a risk of explosion. Do not exceed the recommended service pressure.
3.4 Noise levels.
Precautions must be taken during installation to avoid generating additional noise
and vibration:
• units must be securely mounted on a stable, rigid base,
• connecting pipe work must be sufficiently flexible to ensure vibration is not transmitted to the rest of
the installation.
7
Содержание Sliding unit Series
Страница 2: ......
Страница 5: ...2 5 MAXIMUM ADDITIONAL LOAD ON DRAWER IS 30 KG 3...
Страница 27: ...Embraco Sliding unit 1 1 1 1 2 EMBRACO 2 2 1 1 2 2 6A 3 3 1 3 2 M 3 3 200 2 3 4 27...
Страница 28: ...EMBRACO 3 5 A3 3 6 3 3 7 EMBRACO 10 T EMBRACO e NF C15 100 3 8 DIN NF CIS 100 60204 lEC 60335 28...
Страница 29: ...EMBRACO 4 3 9 4 4 1 4 2 200 4 3 4 5 R 404A 2 R 134a 1 2 3 4 5 6 1 2 3 4 5 29...
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......