HMI Moisture Liquid Indicator
General Information
Only one indicated element is required for all common
refrigerants. This element is highly sensitive to moisture
and will gradually change color in direct relation to an
increase or decrease in the moisture content of the sys-
tem. The dry-caution-wet system operating conditions
are then easily determined by matching the element
color with the two colors displayed on the reference
label. Colors change as often as the system moisture
content changes.
MWP - 680 psig
IMPORTANT: 12 hours is recommended after installation
of the Moisture Liquid Indicator before attempting to
determine the system moisture content.
Safety Instructions
1. Read all instructions thoroughly. Failure to comply
can result in valve failure, system damage, or
personal injury.
2. The indicator element will indicate an unsafe
condition before installation. This is normal and
simply reflects the room humidity condition.
3. The exclusive fused glass eyepiece in the Moisture
Liquid Indicator provides a clear, wide-angle view of the
liquid refrigerant flow so that bubbles or flash gas are
easily seen. This indicates an insufficient system
charge, low head pressure, insufficient liquid subcooling
or some form of restriction in the liquid line.
Installation Instructions
1. The Moisture Liquid Indicator may be installed
anywhere in the liquid line and in any position. It is
normally installed downstream from the filter-drier and
immediately ahead of the thermal expansion valve.
2. Extended cooper connections with bar stock body
permits use of any soft solder or commonly used
brazing alloys. When soldering or brazing, direct the
flame away from the body. Wet rags or chill blocks must
be used when brazing to prevent damaging the Moisture
Liquid Indicator. See Figure 1.
Following installation of a Moisture Liquid Indicator or an
K filter-drier, the system should be allowed to reach
equilibrium as previously noted. If a caution or wet
system condition is still indicated following this period,
the filter-drier or the replaceable cores should be
replaced. This practice should be continued until the
system has dried and a safe condition is indicated.
CAUTION
: This product is intended for use on all
CFC, HCFC and HFC refrigerants. Do not use on any
unlisted fluid media without prior approval of the
Emerson Climate Technologies Flow Controls Division
Applications Engineering Department. Use on fluids
not listed above could result in deterioration of the
moisture indicator element. Not for use on refrigerants
classified by ASHRAE standard 34 as Class A1/A2,
A2, A3, B2 and B3.
Содержание Sliding unit Series
Страница 2: ......
Страница 5: ...2 5 MAXIMUM ADDITIONAL LOAD ON DRAWER IS 30 KG 3...
Страница 27: ...Embraco Sliding unit 1 1 1 1 2 EMBRACO 2 2 1 1 2 2 6A 3 3 1 3 2 M 3 3 200 2 3 4 27...
Страница 28: ...EMBRACO 3 5 A3 3 6 3 3 7 EMBRACO 10 T EMBRACO e NF C15 100 3 8 DIN NF CIS 100 60204 lEC 60335 28...
Страница 29: ...EMBRACO 4 3 9 4 4 1 4 2 200 4 3 4 5 R 404A 2 R 134a 1 2 3 4 5 6 1 2 3 4 5 29...
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......