SINUS PENTA
REGENERATIVE
APPLICATION
71/
140
0
1
2
3
4
2.10.2.
C
OMMISSIONING OF THE
D
RIVE
U
SED AS A
R
EGENERATIVE
B
RAKING
U
NIT
The SINUS PENTA for the regenerative application is factory-set as in
Table 1. For different rated voltage/frequency values, parameters concerning the electric mains must be set up
before activating the drive. When the drive is used as a braking unit, the motor drive activation is not affected
by the regenerative drive (see wiring diagram).
1) Wiring:
Follow the instructions given in the sections of this manual covering the drive wiring
diagrams.
CAUTION
Wrong wiring can cause the equipment malfunction.
2) Power on:
Power on the drive; the link to the ENABLE input (terminal 15) is to be open, so that the
drive is disabled.
Make sure that the drive is set up for the regenerative application: this is shown on the
start page (see below; line 1 states that the regenerative unit is waiting for the Enable
signal) or on the product ID screen in the IDP menu.
R E G E N .
W A I T
E N A
M 0 0 6 = +
5 6 4 . 0 V
M 0 0 7 =
4 0 0 . 0 V
[ M E A ] P A R
C F
I D P
3) Parameter
alteration:
Access the P000 parameter (Key Parameter) and make sure that its setting is as P002. Use
the ESC,
↓
,
↑
and SAVE/ENTER keys to access the drive parameters. See the “Menu Tree”
section in this manual.