P510 DC-bus Voltage Regulator
→
Proportional Term with Min. Error
P510
Range
0
÷
65000
0
÷
65.000
Default
Depends on size and voltage class.
Level
ENGINEERING
Address
620
Function
This parameter sets the proportional term of the DC-bus voltage regulator
for an error lower than or equal to the min. error threshold.
P510=1: with a regulation error of 1V of the DC-bus voltage, the drive
shall deliver 1A current.
If the min. error threshold is the same as the max. error threshold
(P514=P515), the proportional term used by the regulator is always
P510.
P511 DC-Bus Voltage Regulator
→
Integral Term with Min. Error
P511
Range
0
÷
65000
0
÷
649.99 ms with 650.00
→
Disable
Default
Depends on size and voltage class.
Level
ENGINEERING
Address
621
Function
This parameter sets the integral term of the DC-bus voltage regulator.
P512 DC-Bus Voltage Regulator
→
Proportional Term with Max. Error
P512
Range
0
÷
65000
0
÷
65.000
Default
Depends on size and voltage class.
Level
ENGINEERING
Address
622
Function
This parameter sets the proportional term of the DC-bus voltage
regulator.
P512=1: with a regulation error of 1V of the DC-bus voltage, the drive
shall deliver 1A current.
It activates and can be displayed only if P515>P514.
P513 DC-Bus Voltage Regulator
→
Integral Term with Max. Error
P513
Range
0
÷
65000
0
÷
649.99 ms with 650.00
→
Disable
Default
Depends on size and voltage class.
Level
ENGINEERING
Address
623
Function
This parameter sets the integral term of the DC-bus voltage regulator.
It activates and can be displayed only if P515>P514.