RIGENERATIVE
SINUS PENTA
APPLICATION
102/
140
0
1
2
3
4
0
1
2
3
4
P565 Max. Frequency Reset Time
P565
Range
40
÷
1000
0.040
÷
1.000 s
Default
100
0.100 s
Level
ENGINEERING
Address
685
Function
This is the time when the max. frequency reset condition is maintained to
deactivate the mains Max. Frequency fault.
P566 Min. Frequency Trip Threshold
P566
Range
-200
÷
-10
-2.00
÷
-0.10 Hz
Default
-30
-0.30 Hz
Level
ENGINEERING
Address
686
Function
This parameter sets the max. frequency value if compared to the rated
frequency which determines the mains Min. Frequency fault.
P567 Min. Frequency Release Ratio
P567
Range
1000
÷
1006
1.000
÷
1.006
Default
1002
1.002
Level
ENGINEERING
Address
687
Function
This parameter sets the ratio between the trip frequency for the Min.
Frequency fault and its reset value.
P568 Min. Frequency Trip Time
P568
Range
40
÷
1000
0.040
÷
1.000 s
Default
80
0.080 s
Level
ENGINEERING
Address
688
Function
This is the time when the min. frequency trip condition is maintained for the
mains Min. Frequency fault.
P569 Min. Frequency Reset Time
P569
Range
40
÷
1000
0.040
÷
1.000 s
Default
100
0.100 s
Level
ENGINEERING
Address
689
Function
This is the time when the min. frequency reset condition is maintained to
deactivate the mains Min. Frequency fault.