SINUS PENTA
REGENERATIVE
APPLICATION
81/
140
0
1
2
3
4
M545 Active Power, Phase R
M545
Range
±
32000
±
3200.0 kW
Address
1695
Function
Active Power in phase R.
M546 Reactive Power, Phase R
M546
Range
±
32000
±
320.00 kVAR
Address
1696
Function
Reactive Power in phase R.
M547 Apparent Power, Phase R
M547
Range
±
32000
±
3200.0kVA
Address
1697
Function
Apparent Power in phase R.
M548 Power Factor, Phase R
M548
Range
±
100
±
1.00
Address
1698
Function
Power factor in phase R (ratio between the Active Power and the Apparent
Power).
M549 RMS Voltage, Phase R
M549
Range
±
32000
±
3200.0V
Address
1699
Function
Root mean square of the line voltage, phase R.
M550 RMS Current, Phase R
M550
Range
±
32000
±
3200.0A
Address
1700
Function
Root mean square of the line current, phase R.
M551 Active Power, Phase S
M551
Range
±
32000
±
3200.0kW
Address
1701
Function
Active Power in phase S.