3.6.
MAINS MONITOR MENU
3.6.1.
O
VERVIEW
The Mains Monitor menu includes the parameters defining the max. variation thresholds of the mains ratings if
compared to the rated values (Rated Mains Voltage, C500; Rated Mains Frequency, C501) during the
equipment operation.
The mains frequency/voltage values are monitored, which must not exceed or drop below the ranges set in the
parameters of the Mains Monitor menu. Alarm trip can be disabled by setting C502 = NO (C502 is factory
set to YES); in that case, when the mains is out of range, the regenerative drive is temporarily disabled but no
alarm trips (the motor drive enable depends on C503). Parameters P570 to P574 set the
activation/deactivation of each control (factory setting: all controls are activated).
3.6.2.
L
IST OF
P
ROGRAMMABLE
P
ARAMETERS
P550
TO
P574
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P550
Max. Voltage Trip Threshold
ENGINEERING
670
120% Vn
P551
Max. Voltage Release Ratio
ENGINEERING
671
0.920
P552
Max. Voltage Trip Time
ENGINEERING
672
0.150 s
P553
Max. Voltage Reset Time
ENGINEERING
673
0.100 s
P554
Min. Voltage Trip Threshold
ENGINEERING
674
80% Vn
P555
Min. Voltage Release Ratio
ENGINEERING
675
1.125
P556
Min. Voltage Trip Time
ENGINEERING
676
0.150 s
P557
Min. Voltage Reset Time
ENGINEERING
677
0.100 s
P558
Instantaneous Undervoltage Trip Threshold ENGINEERING
678
60% Vn
P559
Instantaneous Undervoltage Release Ratio
ENGINEERING
679
1.060
P560
Instantaneous Undervoltage Trip Time
ENGINEERING
680
0.010 s
P561
Instantaneous Undervoltage Reset Time
ENGINEERING
681
0.010 s
P562
Max. Frequency Trip Threshold
ENGINEERING
682
0.30 Hz
P563
Max. Frequency Release Ratio
ENGINEERING
683
0.998
P564
Max. Frequency Trip Time
ENGINEERING
684
0.080 s
P565
Max. Frequency Reset Time
ENGINEERING
685
0.100 s
P566
Min. Frequency Trip Threshold
ENGINEERING
686
– 0.30 Hz
P567
Min. Frequency Release Ratio
ENGINEERING
687
1.002
P568
Min. Frequency Trip Time
ENGINEERING
688
0.080 s
P569
Min. Frequency Reset Time
ENGINEERING
689
0.100 s
P570
Undervoltage Alarm Enable
ENGINEERING
690
1: On
P571
Min. Voltage Alarm Enable
ENGINEERING
691
1: On
P572
Max. Voltage Alarm Enable
ENGINEERING
692
1: On
P573
RMS Alarm Enable
ENGINEERING
693
1: On
P574
Frequency Alarm Enable
ENGINEERING
694
1: On
Table 10: List of parameters P550 to P574.