SINUS PENTA
REGENERATIVE
APPLICATION
79/
140
0
1
2
3
4
M516 Mains Status 2
M516
Range
0
÷
01FFh
Bit-controlled measure
Address
1666
Function
This parameter displays the status of the Mains Faults (see the MAINS
Bit n.
Description
0
Phase R, max. voltage
1
Phase S, max. voltage
2
Phase T, max. voltage
3
Phase R, min. voltage
4
Phase S, min. voltage
5
Phase T, min. voltage
6 Max.
frequency
7 Min.
frequency
8 PLL
Fault
Table 3: Bits of measure M516.
M517 Mains Status 1
M517
Range
0
÷
007Fh
Bit-controlled measure
See Table 4.
Address
1667
Function
This parameter displays the status of the Mains Faults (see the MAINS
PARAMETERS MENU).
Bit N.
Description
0
Phase R Undervoltage
1
Phase S Undervoltage
2
Phase T Undervoltage
3
Phase R RMS Fault
4
Phase S RMS Fault
5
Phase T RMS Fault
6 PLL
Fault
Table 4: Bits of measure M517.