RIGENERATIVE
SINUS PENTA
APPLICATION
90/
140
0
1
2
3
4
0
1
2
3
4
P520 DC-bus Current Limit
P520
Range
0
÷
1000
0
÷
100.00%
Default
1000
100.00%
Level
ENGINEERING
Address
630
Function
This parameter allows limiting the DC-bus current expressed as a
percentage of the current relating to the size of the drive being used.
P521 DC-bus Current Regulator
→
Proportional Term
P521
Range
0
÷
65000
0
÷
65000
Default
Depends on the drive size.
Level
ENGINEERING
Address
631
Function
This parameter sets the proportional term of the DC-bus current regulator.
P513 DC-bus Current Regulator
→
Integral Term
P522
Range
0
÷
65000
0
÷
649.99 ms with 650.00
→
Disable
Default
Depends on the drive size.
Level
ENGINEERING
Address
632
Function
This parameter sets the integral term of the DC-bus current regulator.