SINUS PENTA
REGENERATIVE
APPLICATION
83/
140
0
1
2
3
4
M577 Power Factor, Phase T
M577
Range
±
100
±
1.00
Address
1727
Function
Power factor in phase T (ratio between the Active Power and the Apparent
Power).
M578 RMS Voltage, Phase T
M578
Range
±
32000
±
3200.0V
Address
1728
Function
Root mean square of the line voltage in phase T.
M579 RMS Current, Phase T
M579
Range
±
32000
±
3200.0A
Address
1729
Function
Root mean square of the line current in phase T.
3.2.4.
M
ENU N
.3
–
DC
M
EASURES
This submenu can be viewed only if parameter R023=2:XMDO+Pout or 4:XMDO+PT100+Pout or
6:XMDO+ADE+Pout (see the EXPANSION BOARD CONFIGURATION MENU).
ES847 option board and additional external components must be installed to view the measures in this
submenu (please refer to the Sinus Penta’s Installation Instructions manual).
M582 DC Current
M582
Range
±
32000
±
3200.0A
Address
1732
Function
Calculation of the DC current measured with an optional, external current
transducer.
Positive sign for the Regenerative Penta output current.
M583 DC Power
M583
Range
±
32000
±
3200.0kW
Address
1733
Function
Calculation of the power delivered based on Idc (M582) and Vdc (M501).
Positive sign for the Regenerative Penta output power.
M584 Performance
M584
Range
±
1000
±
100.0%
Address
1734
Function
Calculation of the system performance—ratio between the Active Power
exchanged with the AC mains (M541) and the DC power (M583).