SINUS PENTA
REGENERATIVE
APPLICATION
43/
140
0
1
2
3
4
0179 295 40
25-30
185
(400kcmils)
400 400 350
0200 295 40
25-30
210
(400kcmils)
400 400 400
0216 315 40
25-30 500
630
450
S40
0250 325
70÷240
(2/0AWG÷500kcm
ils)
40 25-30
240 (500kcmils)
630 630 450
0312 480 DC
Bus -
30 2x150
(2x300kcmils)
800 630 550
0366 540
DC Bus
- 30
2x210
(2x400kcmils)
800 800 600
S50
0399 560
DC Bus
- 30
2x240
(2x500kcmils)
800 800 700
0457 720
DC Bus
- 30
2x240
(2x500kcmils)
1000 800 800
S60
0524 800
DC Bus
- 35
3x210
(3x400kcmils)
1250 1000 1000
0598 900
DC Bus
- 35
3x210
(3x400kcmils)
1250 1250 1000
0748 1000
DC Bus
- 35
1250 1250 1200
S64
0831 1200
DC Bus
- 35
3x240
(3x500kcmils)
1600 1600 1350
0964 1480
DC Bus
- 35 2x3x210
(3x400kcmils
2000 2000 2*800
1130 1700
DC Bus
- 35 2x3x210
(3x400kcmils
2000 2000
2*1000
S74
1296 1950
DC Bus
- 35 2x3x240
(3x500kcmils
2500 2500
2*1200
CAUTION
Always use the correct cable cross-sections and enable the protecting devices
provided for the drive. Failure to do so will cause the non-compliance to
standard regulations of the system where the drive is installed.
NOTE
Make sure that the pre-charge contactor coil can be controlled by the relay
installed on the drive (250VAC-3A/30VDC-3A); if this is not the case, use an
additional external relay. Always use a noise filter parallel-connected to the
contactor coil.