Chapter 6 Parameter Description
77
100% per
−
unit value of the inverter.
Since the using methods of curve 1 and curve 2 are identical, Curve 1 is described as an example here.
Both curve 1 and curve 2 can be used in process open loop analog frequency reference, and the running
frequency of the inverter can be determined by the analog values AI1 and AI2. The conversion
relationship between analog value and setup frequency is as shown in the figures below:
Input percentage %
AIn (0
~
20mA)
A0
A1
20mA
100%
Input analog
value
0
Input percentage %
AIn (0
~
10V)
DI (0
~
P5.10)
A0
A1
Input analog
value
0
10V or
P5.10
100%
Fig.6
−19 Corresponding
percentage of input analog
value (voltage/frequency)
Fig.6
−20 Corresponding
percentage of input analog
value (current)
A0(P6.01)
A1(P6.03)
f0(P6.02)
f1(P6.04)
Ain
、
DI
Setup frequency f
A0(P6.01)
A1(P6.03)
f0(P6.02)
f1(P6.04)
AIn
、
DI
Setup frequency f
Fig.6
−21 Setup
frequency characteristics curve
(positive effect)
Fig.6
−22 Setup
frequency characteristics curve
(negative effect)
P6.01
Curve 1 input point A0
0.0 ~110.0 %(0.0%)
P6.02
Reference frequency f0 corresponding to curve 1 input point A0
0.00~ 300.00 Hz(0.00Hz)
P6.03
Curve 1 input point A1
0.0 ~110.0 %(100.0%)
P6.04
Reference frequency f1 corresponding to curve 1 input point A1
0.00 ~ 300.00 Hz(50.00Hz)
P6.05
Curve 2 input point A0
0.0 ~110.0 %(0.0%)
P6.06
Reference frequency f0 corresponding tocurve 2 input point A0
0.00 ~300.00 Hz(0.00%)
P6.07
Curve 2 input point A1
0.0 ~110.0 %(100.0%)
P6.08
Reference frequency f1 corresponding to curve 2 input point A1
0.00 ~ 300.00 Hz(50.00Hz)