V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 5 List of Parameters
50
Function
code
number
Function code name
Factory
setting
Setting range Unit Property
Function code selection
User
setting
d1.11
Reserved
Factory
0~65535
/
*
0~65535
Group d2 Use of Display Parameters
d2.00
Temperature of heatsink
1
0.0
0.0 ~ 100.0
ºC
*
0.0 ~ 100.0ºC
d2.01
Terminal count value
0
0 ~ 65535
/
*
0~65535
d2.02
AI1 percentage after
curvilinear
transformation
0.0
0.0 ~ 100.0
%
*
0.0~100.0%
d2.03
AI2 percentage after
curvilinear
transformation
0.0
0.0 ~ 100.0
%
*
0.0~100.0%
d2.06
Operation panel
∧/∨
digital adjustment value
0
0 ~ 65535
/
*
0~65535
d2.07
Terminal UP/DN digital
adjustment volume
0
0 ~ 65535
/
*
0~65535
d2.08
User continuous
running time
0
0 ~ 65535
min
*
0~65535
d2.09
User summation
running time
0
0 ~ 65535
min
*
0~65535
d2.10
Reference voltage 1
(percentage)
Factory
0.0~100.0
%
*
0.0~100.0%
d2.11
Reference voltage 2
(percentage)
Factory
0.0~100.0
%
*
0.0~100.0%
d2.12
AI failure source display Factory
0~5
/
*
1: AI1 exceeding limit;
2: AI2 exceeding limit;
3 ~ 5: Reserved
d2.13
Current detection failure
source display
Factory
0~6
/
*
2: Phase W abnormal;
4: Phase V abnormal;
6: Phase U abnorma
d2.14
Frequency corresping
to motor current speed
0.00Hz
0 ~ 655.35
Hz
*
0 ~ 655.35Hz
Group H0 Special Parameters for Constant Pressure Control
H0.00
Closed
−
loop function
selection for constant
pressure control
0
0 ~ 1
/
*
0: Invalid 1: Valid
H0.01
The pressure value
corresponding to
maximum analog
1.00
0.00 ~ 655.35
Mpa
*
0.00 ~ 655.35 Mpa
H0.02
Upper limit of
pressure reference
1.00
0.00 ~ 655.35
Mpa
*
0.00 ~ 655.35 Mpa
H0.03
Lowr limit of
pressure reference
0.00
0.00 ~ 655.35
Mpa
*
0.00 ~ 655.35 Mpa
H0.04
Pressure reference
channel selection
0
0 ~ 2
/
○
0: Digital reference(H0.05);
1: AI1 analog reference;
2: AI2 analog reference
H0.05
Pressure digital
reference
0.04
0.00 ~ 655.35
Mpa
○
0.00 ~ 655.35Mpa(when H0.04=0)
H0.06
Sleeping frequency
reference
30.00
0.0 ~ 300.00
Hz
○
0.0 ~ 300.00Hz
H0.07
Enter sleeping delay
time
60.0
0.0 ~ 3600.0
s
○
0.0 ~ 3600.0s
H0.08
Wake up pressure
percentage reference
50.0
0.0 ~ 200.0
%
○
0.0 ~ 200.0%
H0.09
Wake up delay time
30.0
0.0 ~ 3600.0
s
○
0.0 ~ 3600.0s
H0.11
The frequency of auto
switch acceleration time
and deceleration time
0.00
0.00 ~ 300.00
Hz
○
0.00 ~ 300.00Hz