Chapter 6 Parameter Description
70
Multi
−
functional input terminal definition table:
SN
Function definition
SN
Function definition
0
Jog forward
25
Shutdown via terminal with DC braking 1
1
Jog reverse
26
Emergency shutdown 1 (fastest shutdown)
2
Forward (FWD)
27
Shutdown via terminal with DC braking 2
3
Reverse (REV)
28
Counter trigger input
4
Three
−
wire operation control
29
Counter trigger reset
5
Reserved
30~31
Reserved
6
Multi
−
section digital voltage terminal 1
32
Forced wake up input
7
Multi
−
section digital voltage terminal 2
33~47
Reserved
8
Multi
−
section digital voltage terminal 3
48
Command switching to operation panel
9
Multi
−
section frequency terminal 1
49
Command switching to terminal
10
Multi
−
section frequency terminal 2
50
Command switching to host computer
11
Multi
−
section frequency terminal 3
51
Main frequency source close loop and open
loop switching input
12
Multi
−
section frequency terminal 4
52
Main frequency source switching to digital
13
Acceleration/deceleration terminal 1
53
Reserved
14
Acceleration/deceleration terminal 2
54
Main frequency source switching to AI1
15
Digital regulating frequency reset
55
Main frequency source switching to AI2
16
Frequency increase instruction
56~57
Reserved
17
Frequency decrease instruction
58
Auxiliary frequency source switching to
disabled
18
Acceleration and deceleration disable
instruction
59
Reserved
19
External failure input
60
Auxiliary frequency source switching to AI1
20
Terminal failure reset input
61
Auxiliary frequency source switching to AI2
21
External interrupt contact input
62~66
Reserved
22
Inverter running disabled
67
Closed loop output forced to be 0
23
Shutdown via terminal
68
PID positive or negative function
24
Free shutdown via terminal
69~98
Reserved
Relevant term explanation:
Terminal Xi: Refers to any of terminal X1, X2, X3, X4, also called terminal X.
Terminal Yi: Refers to terminal Y1or relay also called terminal Y.
Terminal function enabled: Means that terminal Xi has set the function under description. And P7.25
adopts the leave
−
factory value, the terminal is closed; when the P7.25 adopts the non
−
leave
−
factory
value, the terminal is open.
Terminal function disabled: Means that terminal Xi has not set the function under description; or it has set
the function, but when P7.25 adopts the leave
−
factory value, the terminal is open; or when the P7.25
adopts the non
−
leave
−
factory value, the terminal is closed.
The leave
−
factory setting of terminal Xi (i=1~4) is no function (function code set as 99).
0: Terminal jog forward input
1: Terminal jog reverse input
2: Terminal forward run input (FWD)
3: Terminal reverse run input (REV)
The functions of above items 0 to 3 are only enabled in the terminal running command reference mode
(P0.06=1). Interlocking of running command and jog command means that the jog command will not be