V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 6 Parameter Description
99
Display of operational panel
Unit place
Arrive continuous running time:
0: Continue running; 1: Stop and alarm
Tens place
Arrive summation running time:
0: Continue running; 1: Stop and alarm
This function code use for inverter automatic stop and alarm or continue running once running time reach
the user preset time. The function code Pb.13, Pb.14 defaults to 0, not timing.
From the inverter to respond the running command, continuous running time reach continuous running
time reference (Pb.13), can output this signal through Y1 terminal or relay terminal , and the Y1 terminal
function number (P7.00) or relay terminal function number (P7.02) set to 18: arrive continuous running
time.
From the inverter power on, running time reach summation running time reference (Pb.14), can output this
signal through Y1 terminal or relay terminal, and the Y1 function number (P7.00) or relay terminal
function number (P7.02) set to 17: arrive summation running time.
Note:
◆
Summation running time and continuous running time will be reset to 0 if power off.
◆
Continuous running time will be reset to 0 in stopping status even power on. If continuous running
time output signal is valid, will become invalid in stopping status and be reset to 0.
◆
Summation running time will not be reset to 0 in stopping status. If summation running time output
signal is valid, will become invalid in stopping status and be reset to 0.
0: No action after power resumes normal.
1: Action after power resumes normal.
The function supports automatic operation of the inverter upon power resume normal after power failure.
Be careful in using this function.
When restart after power failure is selected, the inverter will operate automatically after power on under
any operating command reference mode, such as operation panel operating command reference,
terminal operating command reference or host computer operating command reference.
When restart after power failure is selected, if P0.06=1 and the running terninal is enable when power on,
the inverter will be run after power resumes normal.
Note: To ensure this function is valid under terminal operating command reference mode, please do not
change the status of operating command terminal during shutdown.
When the inverter operates, the function can response the setting of reference channel for other
frequencies after using the pre
−
set frequency as the setting frequency and keeping the time as pre
−
set
frequency operating time Pb.18.
Pb.15
Restart automatically after power resumes normal
0~1(0)
Pb.16
Waiting time for restart
0.0~20.0 s(05.s)
Pb.17
Pre-set frequency
0.00~300.00 Hz(0.00Hz)
Pb.18
Pre-set frequency operating time
0.0~3600.0 s(0.0s)