Chapter 6 Parameter Description
101
Note:
◆
This function is only valid when setting P0.03 to 0
◆
The larger forced saving rate settings, the lower inverter automatically determines the
frequency upper limit.
Parameters copy function can be realized through operation panel.
0: No operation. When upload or download completed, the parameter restores automatically to 0.
1: Upload parameters. Press PRG button to upload parameters to the operation panel after setting, and
will display percentage of copy process when indicating “LoAd”.
2: Download parameters (without motor’s parameters). Press PRG button to download parameters to the
inverter after setting, and will display percentage of copy process when indicating “LoAd”. Parameters of
motor (P9 Group) will not be downloaded to the inverter with this operation.
3: Download parameters (all users’ parameters). Press PRG button to download parameters to the
inverter after setting, and will prompt percentage of copy process when indicating “CoPy”.
4: Parameters blocking enabled (upload not allowed). Avoiding deleting parameters that have been
copied to the operation panel if you upload data unconsciously again. After setting this function, “HoLd”
will be displayed on the operation panel when conducting parameters upload if you do not carry out
unblocking parameters blocking function (upload allowed).
5: Unblocking parameters blocking (upload allowed), allowing uploading parameters to the operation
panel after setting.
Note:
After completing the above settings, Pb.23 will be automatically returned to “0: no action”.
‘’E.CPy” will display if error occur during copies.
The parameters for E5 inverter, V5 inverter and V6 inverter cannot be copied each other.
The copy operation can be performed only when the operation panel copy identification
codes of the two inverters for upload and download (d1.09) are consistent.
The copy function can be completed only when the inverter is completely powered off and
then powered up after the download of the parameters for copy is completed.
6.13 Communication Parameters (Group PC)
The inverter supports international Modbus RTU protocol. Refer to the appendix.A.
PC.00 determines communication baud rate ranging from 4800~57600bps.
4: 4800bps
5: 9600bps
6: 19200bps
Pb.23
Parameters copy
0~5(0)
PC.00
Communication baud rate
4~8(6)
PC.01
Data format
0~2(0)
PC.02
Local address
1~247(1)