V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 5 List of Parameters
51
Function
code
number
Function code name
Factory
setting
Setting range Unit Property
Function code selection
User
setting
H0.12
Acceleration time and
deceleration time auto
switch selection
1
0 ~ 3
s
○
0: Acceleration time and deceleration
time 0 (P0.08 and P0.09);
1: Acceleration time and deceleration
time 1 (P4.09 and P4.10);
2: Acceleration time and deceleration
time 2 (P4.11 and P4.12);
3: Acceleration time and deceleration
time 3 (P4.13 and P4.14)
H0.30
Sleeping and wake up
mode selection
0
0 ~ 1
/
○
0: Sleeping and wake up mode
according H0.00 setting
1: Sleeping and wake up mode
according function code of H0.31 to
H0.34 setting
H0.31
Wake up pressure
reference
0.00
0.0 ~ 10.00
V
○
0.00 ~ 10.00V
H0.32
Sleeping pressure
reference
0.00
0.0 ~ 10.00
V
○
0.00 ~ 10.00V
H0.33
Wake up delay time
0.0
0.0 ~ 3600.0
s
○
0.0 ~0.0 ~ 3600.0s
H0.34
Sleeping delay time
0.0
0.0 ~ 3600.0
s
○
0.0 ~0.0 ~ 3600.0s
Group A0 User
−
defined Function Code Displayed/hidden Zone Parameters
A0.00
Password of
displayed/hidden zone
of user defined function
code
1
0 ~ FFFF
/
○
0 ~ FFFF
A0.01
Displayed/hidden
function 1 of user
defined function code
FFFF
0 ~ FFFF
/
○
0 ~ FFFF
A0.02
Displayed/hidden
function 2 of user
defined function code
FFFF
0 ~ FFFF
/
○
0 ~ FFFF