V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 6 Parameter Description
102
7: 38400bps
8: 57600bps
PC.01 sets communication format, odd
−
even check.
0: 1
−
8
−
1 format, without check.
1: 1
−
8
−
1 format, even check.
2: 1
−
8
−
1 format, odd check.
PC.02 sets the local address. 0 is the broadcast address, available address “1~247”, 248~255 for
reservation.
6.14 Reserved
6.15 Failure Record Parameters (Group d0)
The inverter can record the latest three fault' code serial number (see 7.1 list of failure and alarm
information) and bus voltage, output current and operation frequency during failures recently occurred for
the ease of Trouble Shooting and repair.
Note: Upon the under
−
voltage display (LU), the parameters of fault type and failure time will not be
saved.
The inverter can record automatically the following information: Total power
−
up time of inverter, total
operation time of inverter, record of maximum temperature of heat
−
sink, record of maximum bus voltage
fluctuation.
6.16 Product Identity Parameters (Group d1)
d0.00
Fault type record 2
0~62(0)
d0.01
0~62(0)
d0.02
(Latest) Fault type record 0
0~62(0)
d0.03
Bus voltage of the latest failure
0~999V (0V)
d0.04
Actual current of the latest failure
0.0~999.9A (0.0A)
d0.05
Operation frequency of the latest failure
0.00~300.00 Hz (0.00Hz)
d0.06
Total power-up time of inverter
0.000~65.535 kh(0.000kh)
d0.07
Total operation time of inverter
0.000~65.535 kh(0.000kh)
d0.08
Record of maximum temperature of heatsink
0.0~100.0
º
C(0.0
º
C)
d0.09
Record of maximum bus voltage fluctuation
0~1000V(0V)
d0.10
Reserved
0.00~300.00Hz(0.00Hz)
d0.11
Reserved
0~5(0)
d1.00
Serial number
0.0~FFF.F(Factory)
d1.01
Software version number of control panel
0.00~99.99(Factory)
d1.03
Software version number of operating panel
0.000~F.FFF(Factory)
Fault type record 1