Chapter 4 Using Instructions of Operation Panel
37
4.9 Running for the First Time
Please follow the procedures to run the inverter for the first time:
Before power up, confirm the
wiring is correct
Setting P0.01=5 restore the
factory setting
Setting max output voltage P0.12 and motor
basic frequency P0.15 according to motor
nameplate
Press
M key for jog operation
If motor running direction is wrong, swap
any two phase wires of motor and then
power up
Press RUN key to run the inverter
Setting motor parameter P9.00 to
P9.04 according to motor nameplate
Press key to stop the inverter
Start
END
STOP/RST
Static tuning or rotating tuning
Setting running frequency P0.05
Setting P0.03 to V/F control
Setting
V/F curve input P4.00
Setting torque boost P0.16
RUN
Press RUN key to start auto
tuning, after tuning stop auto
RUN
M
Setting P9.15=1 to
perform static auto-tuning
Note
:
:
If fault happens, please judge the
fault causes and clear the fault
according to 7.1 Fault and alarm
information list.