Appendix B
Specifications
Copyright © 2007-2013 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49G May 2013
73
A
p
p
e
n
d
i
x
B
Specific ati ons
x
Environment
Ambient Temperature Range
(operating)
-40°C to 70°C [ -40°F to 158°F]
Note:
Rectifier output derates above 50°C and below -10°C [14°F].
The maximum output current of APS12 models with the LVD option is limited to 400A (or less
depending on ambient temperature). See System Output.
Relative Humidity
(operating and storage)
<95% (non condensing)
Dimensions H, W, D
APS6-300/APS6-500
6U, 19” mounting, 335 mm [13.2”]*
APS12-300
9U, 19” mounting, 335 mm [13.2”]*
* Additional clear air space is required at rear for rectifier exhaust air venting. See details on page
Weight
APS6-300/APS6-500
12kg [26.4 lb]*
APS12-300
18kg [40 lb]*
Rectifier module
1.7kg [3.7 lb]
* weight of a typical configuration, excluding rectifiers
System Input
Input Voltage
Refer to the rectifier specifications for range.
220-240V (nominal L-N)
208V (nominal L-L)
Maximum Input Current
(per phase @ V = 175V)
APS6 models
1P+N+PE (220-240V nom.):
72A
2P+PE (208V nom.):
72A
3P+N+PE (220-240V nom.):
24A
3P+PE (208V nom.):
42A
APS12 models
(with two ac
feeds)
1P+N+PE (220-240V nom.):
2 x 72A
2P+PE (208V nom.):
2 x 72A
3P+N+PE (220-240V nom.):
2 x 24A
3P+PE (208V nom.):
2 x 42A
Frequency Range
45-66Hz
Earth Leakage Current (maximum)
1.3mA per rectifier