Access Power Solutions Installation and Operation Guide (APS6-300/500 and APS12-300 Series)
74
Copyright © 2007-2013 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49G May 2013
System Output
Output Voltage (nominal)
Dependent on rectifier model.
24V or 48V
Output Voltage Range
21.5 - 32V / 43 - 57.5V
Output Power (maximum)
APS6-300 models:
No LVD:
With LVD:
8.9kW* @ 48V
8.6kW* @ 48V
APS6-500 models:
8.64kW* @ 28.8V or 12.0kW* @ 48V
APS12-300 models:
No LVD:
17.2kW* @ 48V
With LVD:
17.2kW* @ 48V up to 40°C [104°F] ambient
16.1kW* @ 48V up to 45°C [113°F] ambient
15.0kW* @ 48V up to 50°C [122°F] ambient
Load Current (maximum)
APS6-300 models
Total Load
Essential (Priority) Load
Non-essential (Non-priority) Load
APR48-3G (48V)
187A
187A
187A
APR48-ES (48V)
187A
187A
187A
APR24-3G (24V)
-
-
-
APS6-500 models (48V)
Total Load
Essential (Priority) Load
Non-essential (Non-priority) Load
187A
187A
187A
210A**
210A**
210A**
280A
200A
200A
APS12-300 models
Total Load
Essential (Priority) Load
Non-essential (Non-priority) Load
360A
270A
270A
360A
270A
270A
-
-
-
* subject to the maximum load currents as specified
** must include a minimum of three battery MCBs when battery connected