Access Power Solutions Installation and Operation Guide (APS6-300/500 and APS12-300 Series)
102
Copyright © 2007-2013 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49G May 2013
Notes
1
Ensure Alarm Tracking is disabled. Ensure Temperature Compensation is enabled.
2
If the load is not connected to the load MCBs and if an electronic Fuse Fail detect circuits is
installed, this test can also be performed as follows:
Turn off the load MCB
Connect a high impedance path >100k
) between the end load side of the MCB and the
Common Bus. (The impedance path can also be created by touching these points with
your hand.)
3
Ensure the battery discharge is high enough. Allow for the recognition time.
4
This alarm will be displayed if the incorrect configuration or incorrect rectifiers are used in
the system. It is not recommended that this be tested as it is very unlikely for an incorrect
configuration to be installed after commissioning.
5
This alarm is originated from the rectifier. It can only be tested by increasing the internal
temperature of the rectifier.
6
These alarms are only available with the external ac metering option.
7
A digital input must be configured for this test to function. See details in the System
Controller Operation Handbook.
Digital Inputs
Test
Test procedure
Adjustment
Digital Input 1
Change the state of the Digital input.
Ensure any alarms mapped to the digital output (relay)
activate.
Ensure the Digital Input Alarm Name is correct.
Digital Input 2
As for Digital Input 1.
Digital Input 3
As for Digital Input 1.
Digital Input 4
As for Digital Input 1.
Digital Input 5
As for Digital Input 1.
Digital Input 6
As for Digital Input 1.
User Assigned
Digital Inputs
Note 1
As for Digital Input 1.
Check the severity and digital output (relay) mapping is
correct.
Notes
1
As the Digital Inputs can be configured for many different digital input devices, specific
tests have not been detailed on this test sheet.