Commissioning
Copyright © 2007-2013 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49G May 2013
97
Test
Test procedure
Adjustment
Current Share
Note 6
View the individual rectifier currents with the SC200 or
SC100 or DCTools/Web.
Ensure the currents are all at 0 amps.
Connect load to the system.
Ensure that all rectifiers share the load evenly and any
variation is within specification.
None
Battery Test
Set the
Battery Test Interval
to 0 days.
Set the
Battery Test Duration
to 30 minutes
Set the
Battery Test Termination Voltage
to a value
approximately 2 volts below the float voltage.
Connect load to the system.
Start the
Battery Test
.
Ensure the SC200 or SC100 indicates that a
Battery Test
has
started.
Wait until the system voltage reduces below the
Termination
Voltage
.
Confirm the
Battery Test
fails.
Ensure the
Battery Test Fail
alarm is displayed on the SC200
or SC100.
Ensure the
Battery Test
stops and the system voltage returns
to the float voltage setting.
Clear the
Battery Test Fail
alarm in DCTools/Web.
Set the
Battery Test Duration
to 1 minute.
Set the
Battery Test Termination Voltage
to a value
approximately 10 volts below the float voltage.
Connect load to the system.
Start the
Battery Test
.
Ensure the SC200 or SC100 indicates that a
Battery Test
has
started.
Wait for the
Battery Test Duration
time to expire.
Confirm the
Battery Test
passes.
Ensure the
Battery Test
stops and the system voltage returns
to the float voltage setting.
Reset the
Battery Test
settings to the original values.
None
Low Voltage
Disconnect –
Manual Operation
Note 7
Set the LVD manual control to
CONNECT
.
Ensure the LVD contactor is connected.
Ensure the SC200 or SC100 displays an
LVD Manual
alarm.
Ensure the I/O board LVD LED is on.
Set the LVD manual control to AUTO.
Ensure the SC200 or SC100 shows no LVD alarms.
Ensure the I/O board LVD LED is on.
Set the LVD manual control to
DISCONNECT
.
Ensure the LVD contactor disconnects.
Ensure the SC200 or SC100 displays an LVD Manual alarm.
Ensure the I/O board LVD LED is off.
Set the LVD manual control to
AUTO
.
Ensure the LVD connects.
Ensure the SC200 or SC100 shows no LVD alarms.
Ensure the I/O board LVD LED is on.
None
Low Voltage
Disconnect –
Check the LVD contactor is connected.
Increase the
LVD Disconnect Voltage Threshold
.
None