Specifications
Copyright © 2007-2013 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49G May 2013
77
Battery Mid-point Monitoring (SC200 only)
Number of Strings
Standard:
Maximum:
4
24 (with additional IOBGP-01 I/O
boards)
Range
–35V to +35V
Resolution
<30mV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Maximum Cable Length
20m (65 feet)
Low Voltage Disconnect (IOBGP)
Number of contactor connections
2 per IOBGP I/O board
Number of LVD channels
SC100 systems: 2, SC200 systems: 16
Contactor Type
Normally Open (NO) or Normally Closed (NC)*,
with or without auxiliary contacts.
* For NC contactor operation the SC100 and
IOBGP must be powered from the battery side of
the LVD.
Contactor Coil Voltage (nominal)
With auxiliary contacts: 12V, 24V or 48V
Without auxiliary contacts: Equal to nominal
system voltage
Maximum Hold-in Current
1.2A (per contactor)
Maximum Cable Length
3m (10 feet)
Connector
MTA156 (4-way)
Communications
USB (SC200 only)
Version:
Connector:
1.1 (12Mbits/s)
USB B (female)
RS232
Interface:
Connector:
RS232 (DTE)
DB9M
Ethernet (SC200 only)
Interface:
Connector:
Protocols:
10baseT
RJ45
TCP/IP, SNMP, S3P over IP,
http (Web), https (secure Web),
SNTP, Modbus-TCP, Serial
Server
MAC Address:
See details in the System
Controller Operation
Handbook.
Web browser:
Microsoft Internet Explorer 8 or
later (IE6 is compatible but with
reduced performance), Mozilla
Firefox 3.0 or later.
External modem options
Type:
Operation:
PSTN or GSM
Dial in/Dial out on alarm*
* Can operate as a backup for Ethernet communications (SC200 only).