Services
Modbus gateway
IX14 User Guide
403
where
value
is an integer from
0
to
255
. Leave at the default setting of
0
to not adjust the
server address.
If a packet contains a Modbus server address above the amount entered here, the address
will be adjusted downward by this amount before the packet is delivered. This allows you
to configure clients on the gateway that will forward messages to remote devices with the
same Modbus address on different buses. For example, if there are two devices on two
different buses that have the same Modbus address of 10, you can create two clients on
the gateway:
n
Client one:
l
filter
set to
10
.
This will configure the gateway to deliver all messages that have the Modbus server
address of 10 to this device.
n
Client two:
l
filter
set to
20
.
l
adjust_server_address
set to
10
.
This will configure the gateway to deliver all messages that have the Modbus server
address address of 20 to the device with address 10.
i. Repeat the above instructions for additional clients.
6. Save the configuration and apply the change:
(config)> save
Configuration saved.
>
7. Type
exit
to exit the Admin CLI.
Depending on your device configuration, you may be presented with an
Access selection
menu
. Type
quit
to disconnect from the device.
Show Modbus gateway status and statistics
You can view status and statistics about location information from either the WebUI or the command
line.
WebUI
1. Log into the IX14 WebUI as a user with Admin access.
2. On the menu, select
Status
>
Modbus Gateway
.
The
Modbus Gateway
page appears.
Statistics related to the Modbus gateway server are displayed. If the message
Server
connections not available
is displayed, this indicates that there are no connected clients.
n
To view information about Modbus gateway clients, click
Clients
.
n
To view statistics that are common to both the clients and server, click
Common
Statistics
.
n
To view configuration details about the gateway, click the
(configuration) icon in the
upper right of the gateway's status pane.
Содержание IX14
Страница 1: ...IX14 User Guide Firmware version 22 2 ...
Страница 45: ...Configuration and management Exit the command line interface IX14 User Guide 45 Type q or quit to exit ...
Страница 515: ...Monitoring This chapter contains the following topics intelliFlow 516 Configure NetFlow Probe 523 IX14 User Guide 515 ...
Страница 756: ...Routing Virtual Router Redundancy Protocol VRRP IX14 User Guide 756 ...
Страница 803: ...Command line interface Command line reference IX14 User Guide 803 Parameters None ...
Страница 812: ...Command line interface Command line reference IX14 User Guide 812 reboot Reboot the system Parameters None ...