AX - 3 S e r ie s O p e r a t i o n M a n u a l
4 - 2 6
_4
4.2.1.12
System Parameters
Here you can set up the various parameters for the AX-3 Series PLC. Note that settings on this page do NOT support
on-line editing.
I/O module CONFIG by Manual/Max when Power On
You can set the number of I/O modules here.
Manual (default): The actual module placement should be based on the configuration set in HWCONFIG.
If the
settings are matched, the PLC can run normally.
Max: Sets a maximum number for the module placement. An alarm shows if your actual I/O module placement is
larger than the maximum setting.
CPU module Stop when I/O Module No Response
The parameter sets whether the CPU and other normal modules can operate constantly when there is an extension
module, which does not response during offline period.
Stop (default): The CPU module stops running and then shows errors.
Keep Run: The CPU module and other normal modules keep running.
CPU module Stop when I/O Module Occurred Error
The parameter sets the method to deal with a minor error in the extension modules.
Stop: The CPU stops running and sends an error.
Keep Run (default): The CPU keeps running but records the warning message.
Select Action When 24Vdc Input Unstable
What to do when the 24Vdc power is unstable
Continue Running when power stable (default): The CPU stops and waits till the power is stable and then the CPU
begins to run.
Into Error Status: The CPU stops and ERROR LED blinks; even after the power is stable again, the CPU still stays
stop.
Содержание AX-3 Series
Страница 17: ...AX 3 Series Operation Manual 1 10 _1 MEMO...
Страница 54: ...AX 3 Series Operation Manual 3 22 _3 MEMO...
Страница 98: ...AX 3 Series Operation Manual 4 44 _4 MEMO...
Страница 118: ...AX 3 Series Operation Manual 6 8 _6 MEMO...
Страница 148: ...AX 3 Series Operation Manual 7 30 _7 Scan PLC controller Add the newly scanned PLC controller and click OK...
Страница 241: ...Chapter 7 Motion Control Basic Settings Operation 7 123 7_ Click to enter Axis 0 tab on PoAxis Configuration page...
Страница 292: ...AX 3 Series Operation Manual 7 174 _7 Jerk Done MC_MoveSuperImposed_Done Busy CommandAborted Error ErrorID...
Страница 310: ...AX 3 Series Operation Manual 8 18 8_ MEMO...
Страница 355: ...Appendix A Troubleshooting A 5 _A...