AX - 3 S e r ie s O p e r a t i o n M a n u a l
A - 1 2
_A
_A
Error
Code
(16#)
Item Name
Description
Solution
DMC_PresetValue and is not
done yet.
186D3
DFB_PV_CANNOT_
PRESET_WHEN_SAMP
LING
The counter is executing
DFB_Sample.
Disable the sample function of this counter.
Disable DFB_Sample of this counter.
186D4
DFB_PV_SETRING_
NOT_DONE
The counter is executing
DFB_SetRing and is not done
yet.
Execute this function block after the
execution of DFB_SetRing of this counter
completes.
186D5
DFB_PV_INVALID_
PRESET_VALUE
When the encoder of high-
speed counter is a rotary axis
and the pin of "diPresetValue"
exceeds the range.
Set the pin "diPresetValue" of the function
block in the range of [0 ~
EncoderAxis.Modulo Value ].
186D6
DFB_PV_COUNTER_RE
F_CHANGED_
DURING_
OPERATION
The input pin "Counter" has
been changed during the
execution of the function block.
Check if the variable of the pin “Counter”
has been changed after the execution of the
DFB_PresetValue.
186DC
DFB_SP_INVALID_
COUNTER_REF
The variable of the function
block pin is NOT a
Counter_REF type.
Make sure to select
Counter
on the IO
Configuration setting page and import IEC
Object to the pin “Counter” of the function
block DMC_Sample.
186DD
DFB_SP_COUNTER_N
OT_ENABLE
The function block
DFB_Counter is not enabled
yet.
Execute DFB_Sample after making sure this
counter is enabled by DFB_HCnt.
186DE
DFB_SP_ALREADY_SA
MPLING
The counter is executing
DFB_Sample.
Check if this counter is enabled by other
DFB_Sample.
186DF
DFB_SP_PRESET_
NOT_DONE
The counter is executing
DFB_PresetValue and is not
done yet.
Execute this function block after the
execution of DFB_PresetValue of this
counter completes.
186E0
DFB_SP_INVALID_
SAMPLE_TIME
The setting value of input pin
“wSampleTime” of the function
block DFB_Sample exceeds the
range of [10-65535].
Set the pin “wSampleTime” of the function
block DFB_Sample in the range of of [10-
65535].
186E1
DFB_SP_COUNTER_RE
F_CHANGED_
DURING_
OPERATION
The input pin "Counter" has
been changed during the
execution of the function block.
Check if the variable of the pin “Counter”
has been changed after the execution of the
DFB_Sample.
186E7
DFB_SR_INVALID_
COUNTER_REF
The variable of the function
block pin is NOT a
Counter_REF type.
Make sure to select
Counter
on the IO
Configuration setting page and import IEC
Object to the pin “Counter” of the function
block DFB_SetRing.
186E8
DFB_SR_COUNTER_H
AS_NO_CHILD_
ENCODER_AXIS
No child node of the high-speed
counter is connected to the
encoder.
Insert EncoderAxis into the counter and set
the encoder type to rotary axis and
reexecute the function block.
186E9
DFB_SR_COUNTER_N
OT_RING
The encoder of the high-speed
counter is not a rotary axis type.
Select the encoder type to rotary axis on the
Counter Configuration page.
186EA
DFB_SR_PREVIOUS_S
ETRING_NOT_
DONE
The preset counting function of
the counter has been enabled
by other function block
DMC_SetRing and is not done
yet.
Execute this function block after the
execution of DFB_SetRing of this counter
completes.
Содержание AX-3 Series
Страница 17: ...AX 3 Series Operation Manual 1 10 _1 MEMO...
Страница 54: ...AX 3 Series Operation Manual 3 22 _3 MEMO...
Страница 98: ...AX 3 Series Operation Manual 4 44 _4 MEMO...
Страница 118: ...AX 3 Series Operation Manual 6 8 _6 MEMO...
Страница 148: ...AX 3 Series Operation Manual 7 30 _7 Scan PLC controller Add the newly scanned PLC controller and click OK...
Страница 241: ...Chapter 7 Motion Control Basic Settings Operation 7 123 7_ Click to enter Axis 0 tab on PoAxis Configuration page...
Страница 292: ...AX 3 Series Operation Manual 7 174 _7 Jerk Done MC_MoveSuperImposed_Done Busy CommandAborted Error ErrorID...
Страница 310: ...AX 3 Series Operation Manual 8 18 8_ MEMO...
Страница 355: ...Appendix A Troubleshooting A 5 _A...