C h a p t e r 7 M o t i o n C o n t r o l B a s i c S e t t i n g s & O p e r a t i o n
7 - 1 4 1
7_
LD Language
Execute homing under normal output status of MC_Power. Once homing is completed, execute
MC_MoveAbsolute. At the same time, MC_Stop can be excuted for a quick stop if needed, which would
abort MC_MoveAbsolute with state True of CommandAborted output so as to command a deceleration stop
for axis based on the setting of deceleration, then the Done output of MC_Stop shifts to True after the stop
command completed.
ST Language
The process is same as LD. After MC_Home is done, the state would be Standstill.
//MC_Power
MC_Power_0(
Axis:= SM_Drive_Virtual,
Enable:= ServoOn,
bRegulatorOn:= TRUE,
bDriveStart:= TRUE,
Status=> ,
bRegulatorRealState=> ,
bDriveStartRealState=> ,
Busy=> ,
Error=> ,
ErrorID=> );
//MC_Home
IF MC_Power_0.Status THEN
MC_Home_0(
Axis:= SM_Drive_Virtual,
Execute:= MC_Home_0_Execute,
Position:= 0,
Done=> ,
Busy=> ,
CommandAborted=> ,
Error=> ,
ErrorID=>);
END_IF
Содержание AX-3 Series
Страница 17: ...AX 3 Series Operation Manual 1 10 _1 MEMO...
Страница 54: ...AX 3 Series Operation Manual 3 22 _3 MEMO...
Страница 98: ...AX 3 Series Operation Manual 4 44 _4 MEMO...
Страница 118: ...AX 3 Series Operation Manual 6 8 _6 MEMO...
Страница 148: ...AX 3 Series Operation Manual 7 30 _7 Scan PLC controller Add the newly scanned PLC controller and click OK...
Страница 241: ...Chapter 7 Motion Control Basic Settings Operation 7 123 7_ Click to enter Axis 0 tab on PoAxis Configuration page...
Страница 292: ...AX 3 Series Operation Manual 7 174 _7 Jerk Done MC_MoveSuperImposed_Done Busy CommandAborted Error ErrorID...
Страница 310: ...AX 3 Series Operation Manual 8 18 8_ MEMO...
Страница 355: ...Appendix A Troubleshooting A 5 _A...