Particulate
contamination
Specifications
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
Applies to data center and non-data center environments.
Corrosive dust
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
Applies to data center and non-data center environments.
Gaseous
contamination
Specifications
Copper coupon
corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon
corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
32
Technical specifications
Содержание E35S001
Страница 2: ......
Страница 164: ...164 Getting help ...