factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
533 Display text 1 (DISPLAY TEXT ARRAY 1)
Value:
Max. 20 characters
[XXXXXXXX]
Function:
Here, a text of max. 20 characters can be written that
will be shown in display line 1, provided
LCP display
text
[27] has been selected in parameter 007
Large
display read-out
. Example of display text.
Description of choice:
Write the required text via serial communication.
534 Display text 2 (DISPLAY TEXT ARRAY 2)
Value:
Max. 8 characters
[XXXXXXXXXXXXXXXXXXXX]
Function:
Here, a text of max. 8 characters can be written that
will be shown in display line 2, provided
LCP display
text
[27] has been selected in parameter 007
Large
display read-out.
Description of choice:
Write the required text via serial communication.
535 Bus feedback 1 (BUS FEEDBACK1)
Value:
0 - 16384 decimal (0 - 4000 Hex)
★
0
Function:
Via the serial communication port, this parameter
allows writing of a bus feedback value which will then
form part of the feedback handling (see page xx). Bus
feedback 1 will be added to any feedback value
registered on terminal 53.
Description of choice:
Write the required bus feedback value via serial
communication.
536 Bus feedback 2 (BUS FEEDBACK 2)
Value:
0 - 16384 decimal (0 - 4000 Hex)
★
0
Function:
Via serial communication, a bus feedback value could
be written in this parameter that would subsequently
become part of the feedback handling system (see
page xxx). Bus feedback 2 will be added to any
feedback value on terminal 54.
Description of choice:
Write the required bus feedback value via the serial
communication.