VLT
®
6000 HVAC
MG.60.B1.02 - VLT is a registered Danfoss trademark
134
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
507 Selection of Setup (SELECTING OF SETUP)
508 Selection of preset reference
(SELECTING OF SPEED)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
★
Logic or (LOGIC OR)
[3]
Function:
See the functional description under parameter 503
Coasting
.
Description of choice:
The table below shows the Setup (parameter 002
Active Setup
) that has been selected via
Digital input
[0],
Serial communication
[1],
Logic and
[2] or
Logic or
[3].
The table also shows the preset reference
(parameters 211-214
Preset reference
) that has been
selected via
Digital input
[0],
Serial communication
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Bus Bus Setup/Preset Setup/Preset
Setup nr.
msb lsb
msb
lsb
Preset ref. no.
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
1
0
1
0
1
2
0
1
1
0
3
0
1
1
1
4
1
0
0
0
1
1
0
0
1
2
1
0
1
0
3
1
0
1
1
4
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
506 Reversering (REVERSING)
Value:
★
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See the functional description under parameter 503
Coasting
.
Description of choice:
The table below shows when the motor is running
clockwise and anti-clockwise when
Digital input
[0],
Serial communication
[1],
Logic and
[2] or
Logic or
[3]
has been selected.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Kl. 19 com.
Function
Kl. 19 com.
Function
0
0
Clockwise
0
0
Clockwise
0
1
Clockwise
0
1
Clockwise
1
0
Anti-clock.
1
0
Clockwise
1
1
Anti-clock.
1
1
Anti-clock.
Logic and
[2]
Logic or
[3]
Serial
Serial
Kl. 19 com.
Function
Kl. 19 com.
Function
0
0
Clockwise
0
0
Clockwise
0
1
Clockwise
0
1
Anti-clock.
1
0
Clockwise
1
0
Anti-clock.
1
1
Anti-clock.
1
1
Anti-clock.