VLT
®
6000 HVAC
43
MG.60.B1.02 - VLT is a registered Danfoss trade mark
Installation
■
■
■
■
■
General technical data
Control card, pulse input:
No. of programmable pulse inputs ....................................................................................................................... 3
Terminal nos. ......................................................................................................................................... 17, 29, 33
Max. frequency on terminal 17 ........................................................................................................................ 5 kHz
Max. frequency on terminals 29, 33 ............................................................................. 20 kHz (PNP open collector)
Max. frequency on terminals 29, 33 ........................................................................................... 65 kHz (Push-pull)
Voltage level ........................................................................................................... 0-24 V DC (PNP positive logics)
Voltage level, logic ‘0’ ................................................................................................................................ < 5 V DC
Voltage level, logic ‘1’ .............................................................................................................................. > 10 V DC
Maximum voltage on input ........................................................................................................................ 28 V DC
Input resistance, R
i
............................................................................................................................. approx. 2 k
Ω
Scanning time per input ............................................................................................................................. 3 msec.
Resolution ........................................................................................................................................... 10 bit + sign
Accuracy (100-1 kHz), terminals 17, 29, 33 ............................................................... Max. error: 0.5% of full scale
Accuracy (1-5 kHz), terminal 17 .................................................................................. Max. error: 0.1% of full scale
Accuracy (1-65 kHz), terminals 29, 33 ........................................................................ Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse inputs are galvanically isolated from the supply voltage (PELV). In addition,
pulse inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC
supply and opening switch 4. See drawing on page 65.
Control card, digital/pulse and analogue outputs:
No. of programmable digital and analogue outputs ............................................................................................. 2
Terminal nos. ................................................................................................................................................ 42, 45
Voltage level at digital/pulse output ....................................................................................................... 0 - 24 V DC
Minimum load to frame (terminal 39) at digital/pulse output .......................................................................... 600
Ω
Frequency ranges (digital output used as pulse output) ........................................................................... 0-32 kHz
Current range at analogue output ........................................................................................................ 0/4 - 20 mA
Maximum load to frame (terminal 39) at analogue output ............................................................................. 500
Ω
Accuracy of analogue output ...................................................................................... Max. error: 1.5% of full scale
Resolution on analogue output. ....................................................................................................................... 8 bit
Reliable galvanic isolation: All digital and analogue outputs are galvanically isolated from the supply voltage (PELV)
and other high-voltage terminals.
Control card, 24 V DC supply:
Terminal nos. ................................................................................................................................................ 12, 13
Max. load .................................................................................................................................................... 200 mA
Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the
same potential as the analogue outputs.
Control card, RS 485 serial communication:
Terminal nos. .............................................................................................................. 68 (TX+, RX+), 69 (TX-, RX-)
Reliable galvanic isolation: Full galvanic isolation (PELV).
Relay outputs:
No. of programmable relay outputs ...................................................................................................................... 2
Terminal nos., control card ...................................................................................................................... 4-5 (make)
Max. terminal load (AC) on 4-5, control card ............................................................................ 50 V AC , 1 A, 60 VA
Max. terminal load (DC) on 4-5, control card ............................................................................ 75 V DC, 1 A, 30 W
Max. terminal load (AC) on 4-5, control card for UL/cUL applications .................................................. 30 V AC, 1 A
Max. terminal load (DC) on 4-5, control card for UL/cUL applications .............................................. 42.2 V DC, 1 A
Terminal nos., power card and relay card ............................................................................. 1-3 (break), 1-2 (make)
Max. terminal load (AC) on 1-3, 1-2, power card and relay card ............................................. 240 V AC, 2 A, 60 VA
Min. terminal load on 1-3, 1-2, power card and relay card .................................. 24 V DC 10 mA, 24 V AC 100 mA