VLT
®
6000 HVAC
68
MG.60.B1.02 - VLT is a registered Danfoss trade mark
■
■
■
■
■
Connection examples
Single-pole start/stop
- Start/stop using terminal 18.
Parameter 302 =
Start
[1]
- Quick-stop using terminal 27.
Parameter 304 =
Coasting stop, inverse
[0]
Digital speed up/down
- Speed up and down using terminals 32 and 33.
Parameter 306 =
Speed up
[7]
Parameter 307 =
Speed down
[7]
Parameter 305 =
Freeze reference
[2]
Potentiometer reference
- Parameter 308 =
Reference
[1]
Parameter 309 =
Terminal 53, min. scaling
Parameter 310 =
Terminal 53, max. scaling
- Start permitted with terminal 16.
Parameter 300 =
Start enabled
[8].
- Start/stop with terminal 18.
Parameter 302 =
Start
[1].
- Quickstop with terminal 27.
Parameter 304 =
Coasting stop, inverse
[0].
- Activated damper (motor)
Parameter 323 =
Start command active
[13].
Run permissive
2-zone regulation
- Parameter 308 =
Feedback
[2].
- Parameter 311 =
Feedback
[2].
Transmitter connection
- Parameter 314 =
Reference
[1]
- Parameter 315 =
Terminal 60, min. scaling
- Parameter 316 =
Terminal 60, max. scaling