140
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
■
■
■
■
■
Warning words 1+2 and Alarm word
Warning word, extended status word and alarm word
are shown in Hex format on the display. If there is
more than one warning or alarm, a sum of the total
warnings or alarms will be shown.
The descriptions relating to the extended status
word can be seen from page 129, and with respect
to warning word, extended status word and alarm
word, the descriptions can also be read out via the
serial bus in parameter 531
Warning word
, 532
Extended status word
and 529
Alarm word.
Hex code Extended status word
00000001
Overvoltage control active
00000002
Start delay
00000004
Sleep boost active
00000008
Sleep mode active
00000010
Automatic motor adaptation
completed
00000020
Automatic motor adaptation running
00000040
Reversing and start
00000080
Ramp operation
00000100
Reversing
00000200
Speed = reference
00000400
Running
00000800
Local ref. = 0,
Remote controlled ref. = 1
00001000
OFF mode = 1
00002000
Auto mode = 0, Hand mode = 1
00004000
Start blocked
00008000
Start blocked signal missing
00010000
Freeze output
00020000
Freeze output blocked
00040000
Jogging
00080000
Jog blocked
00100000
Stand by
00200000
Stop
00400000
DC stop
00800000
Drive ready
01000000
Relay 123 active
02000000
Drive ready
04000000
Control ready
08000000
Start prevented
10000000
Profibus OFF3 active
20000000
Profibus OFF2 active
40000000
Profibus OFF1 active
80000000
Reserved
Hex code
Warning word
00000001
Reference high
00000002
Fault in EEprom on control card
00000004
Fault in EEprom on power card
00000008
HPFB bus timeout
00000010
Serial communication timeout
00000020
Overcurrent
00000040
Current limit
00000080
Motor thermistor
00000100
Motor overtemperature
00000200
Inverter overtemperature
00000400
Undervoltage
00000800
Overvoltage
00001000
Voltage warning low
00002000
Voltage warning high
00004000
Mains phase fault
00008000
Live zero fault
00010000
Under 10 Volt (terminal 50)
00020000
Reference low
00040000
Feedback high
00080000
Feedback low
00100000
Output current high
00200000
Out of frequency range
00400000
Profibus communication fault
00800000
Output current low
01000000
Output frequency high
02000000
Output frequency low
04000000
AMA - motor too small
08000000
AMA - motor too big
10000000
AMA - check par. 102, 103, 105
20000000
AMA - check par. 102, 104, 106
40000000
Reserved
80000000
Reserved