VLT
®
6000 HVAC
145
MG.60.B1.02 - VLT is a registered Danfoss trade mark
★
= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
Programming
620 Operating mode (OPERATION MODE)
Value:
★
Normal function (NORMAL OPERATION)
[0]
Function with de-activated inverter
(OPER. W/INVERT.DISAB)
[1]
Control card test (CONTROL CARD TEST)
[2]
Initialisation (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter can
be used for two different tests.
Furthermore, it is possible to reset to the default
factory settings for all Setups, except parameters 500
Address
, 501
Baud rate
, 600-605
Operating data
and
615-617
Fault log
.
Description of choice:
Normal function
[0] is used for normal operation of
the motor.
Function with de-activated inverter
[1] is selected if
control is desired over the influence of the control
signal on the control card and its functions - without
the motor shaft running.
Control card [2]
is selected if control of the analogue
and digital inputs, analogue and digital outputs, relay
outputs and the control voltage of +10 V is desired.
A test connector with internal connections is required
for this test.
The test connector for the
Control card
[2] is set up
as follows:
connect 4-16-17-18-19-27-29-32-33;
connect 5-12;
connect 39-20-55;
connect 42 - 60;
connect 45-53-54.
Use the following procedure for the control card test:
1) Select
Control card test
.
2) Cut off the mains supply and wait for the light in
the display to go out.
3) Insert the test plug (see preceding column).
4) Connect to mains.
5) The VLT frequency converter expects the [OK] key
to be pressed (the test cannot be run without
LCP).
6) The VLT frequency converter automatically tests
the control card.
7) Remove the test connector and press the [OK]
key when the VLT frequency converter displays
"TEST COMPLETED".
8) Parameter 620
Operating mode
is automatically
set to
Normal function
.
If the control card test fails, the VLT frequency
converter will display "TEST FAILED". Replace the
control card.
Initialisation
[3] is selected if the factory setting of the
unit is to be generated without resetting parameters
500
Address
, 501
Baud rate
, 600-605
Operating
data
and 615-617
Fault log
.
Procedure for initialisation:
1) Select
Initialisation
.
2) Press the [OK] key.
3) Cut off the mains supply and wait for the light in
the display to go out.
4) Connect to mains.
5) Initialisation of all parameters will be carried out in
all Setups with the exception of parameters 500
Address
, 501
Baud rate
, 600-605
Operating data
and 615-617
Fault log
.
Manual initialisation is another option. See procedure
on page 73.