Parameter 202
Output frequency high limit, f
MAX
is to
be changed to 100 Hz. This value must be remember
after a power failure, so it is written in EEPROM.
PKE =
E0CA Hex - Write to parameter 202
Output frequency high limit, f
MAX
IND =
0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 03E8 Hex - Data value 1000, corre-
sponding to 100 Hz, see
Conversion
.
E0CA H 0000 H 0000 H 03E8 H
The reply from the slave to the master will be:
10CA H 0000 H 0000 H 03E8 H
Example - Choice of a data value:
kW
[20] is to be selected in parameter 415
Process
units
. This value must be remembered after a power
failure, so it is written in EEPROM.
PKE =
E19F Hex - Write to parameter 415
Process units
IND =
0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0014 Hex - Choose data choice
kW
[20]
E19F H 0000 H 0000 H 0014 H
The reply from the slave to the master will be:
119F H 0000 H 0000 H 0014 H
Example - Read a parameter value:
PKE
IND
PWE
HIGH
PWE
LOW
PKE
IND
PWE
HIGH
PWE
LOW
The value in parameter 206
Ramp-up time
is required.
The master sends the following enquiry:
PKE =
10CE Hex - read parameter 206
Ramp-up time
IND =
0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0000 Hex
10CE H 0000 H 0000 H 0000 H
If the parameter value in parameter 206
Ramp-up time
is 10 seconds, the reply from the slave to the master
will be as follows:
10CE H 0000 H 0000 H 000A H