VLT
®
6000 HVAC
133
MG.60.B1.02 - VLT is a registered Danfoss trademark
✭
=
factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
Programming
Description of choice:
The table below shows when the motor is running
and is coasting when
Digital input
[0],
Serial
communication
[1],
Logic and
[2] or
Logic or
[3] has
been selected.
NB!:
Please note that terminal 27 and bit 03 of the
control word are active in the case of logic '0'.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Kl. 27 com.
Function
Kl. 27
com.
Function
0
0
Coasting
0
0
Coasting
0
1
Coasting
0
1
Motor run.
1
0
Motor run.
1
0
Coasting
1
1
Motor run.
1
1
Motor run.
Logic and
[2]
Logic or
[3]
Serial
Serial
Kl. 27 com.
Function
Kl. 27
com.
Function
0
0
Coasting
0
0
Coasting
0
1
Motor run.
0
1
Coasting
1
0
Motor run.
1
0
Coasting
1
1
Motor run.
1
1
Motor run.
Digital input
[0]
Serial communication
[1]
Term. Serial Term.Seriel
19/27 com.
Function
19/27 com.
Function
0
0
DC-brake
0
0
DC-brake
0
1
DC-brake
0
1
Motor run.
1
0
Motor run.
1
0
DC-brake
1
1
Motor run.
1
1
Motor run.
Logic and
[2]
Logic or
[3]
Term. Serial Term.Serial
19/27 com.
Function
19/27 com.
Function
0
0
DC-brake
0
0
DC-brake
0
1
Motor run.
0
1
DC-brake
1
0
Motor run.
1
0
DC-brake
1
1
Motor run.
1
1
Motor run.
505 Start (START)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and(LOGIC AND)
[2]
★
Logic or (LOGIC OR)
[3]
Function:
See the functional description under parameter 503
Coasting
.
Description of choice:
The table below shows when the motor has stopped
and gives the situations in which the VLT frequency
converter has a start command when
Digital input
[0],
Serial communication
[1],
Logic and
[2] or
Logic or
[3]
has been selected.
Digital input
[0]
Serial communication
[1]
Serial
Serial
Kl. 18 com.
Function
Kl. 18 com.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Start
1
0
Stop
1
1
Start
1
1
Start
Logic and
[2]
Logic or
[3]
Serial
Serial
Kl. 18 com.
Function
Kl. 18 com.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Stop
1
0
Start
1
1
Start
1
1
Start
504 DC brake (DC BRAKE)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
★
Logic or (LOGIC OR)
[3]
Function:
See functional description under parameter 503
Coasting
.
Description of choice:
The table below shows when the motor is running
and is DC-braking when
Digital input
[0],
Serial
communication
[1],
Logic and
[2] or
Logic or
[3] has
been selected.
NB!:
Please note that
DC braking inverse
[3] via
terminal 19, terminal 27 and bit 03 of the
control word is active in the case of logic '0'.