= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
MG.60.B1.02 - VLT is a registered Danfoss trade mark
203 Reference site
(REFERENCE SITE)
Value:
★
Hand/Auto linked reference
(LINKED TO HAND/AUTO))
[0]
Remote reference (REMOTE)
[1]
Local reference (LOCAL)
[2]
Function:
This parameter decides which resulting reference is to
be active. If
Hand/Auto linked reference
[0] is selected,
the resulting reference will depend on whether the
VLT frequency converter is in Hand or Auto mode.
The table shows which references are active when
Hand/Auto linked reference
[0],
Remote reference
[1]
or
Local reference
[2] has been selected. The Hand
mode or Auto mode can be selected via the control
keys or via a digital input, parameters 300-307
Digital
inputs.
Reference
handling
Hand mode
Auto mode
Hand/Auto [0]
Local ref. active
Remote ref. active
Remote [1]
Remote ref. active
Remote ref. active
Local [2]
Local ref. active
Local ref. active
Description of choice:
If
Hand/Auto linked reference
[0] is chosen, the motor
speed in Hand mode will be decided by the local
reference, while in Auto mode it depends on remote
references and any setpoints selected.
If
Remote reference
[1] is selected, the motor speed
will depend on remote references, regardless of
whether Hand mode or Auto mode has been chosen.
If
Local reference
[2] is selected, the motor speed will
only depend on the local reference set via the control
panel, regardless of whether Hand mode or Auto
mode has been selected.
204 Minimum reference, Ref
MIN
(MIN. REFERENCE)
Value:
Parameter 100
Configuration = Open loop
[0].
0.000 - parameter 205 Ref
MAX
✭
0.000 Hz
Parameter 100
Configuration = Closed loop
[1].
-Par. 413
Minimum feedback
- par. 205
Ref
MAX
✭
0.000
Function:
The
Minimum reference
gives the minimum value that
can be assumed by the sum of all references. If
Closed
loop
has been selected in parameter 100
Configuration
, the minimum reference is limited by
parameter 413
Minimum feedback
.
Minimum reference is ignored when the local reference
is active (parameter 203
Reference site
).
The unit for the reference can be seen from the
following table:
Unit
Par. 100
Configuration = Open loop
Hz
Par. 100
Configuration = Closed loop
Par. 415
Description of choice:
Minimum reference
is set if the motor is to run at a
minimum speed, regardless of whether the resulting
reference is 0.
205 Maximum reference, Ref
MAX
(MAX. REFERENCE)
Value:
Parameter 100
Configuration = Open loop
[0]
Parameter 204
Ref
MIN
- 1000.000 Hz
✭
50.000 Hz
Parameter 100
Configuration = Closed loop
[1]
Par. 204
Ref
MIN
- par. 414
Maximum feedback
✭
50.000 Hz
Function:
The
Maximum reference
gives the maximum value
that can be assumed by the sum of all references. If
Closed loop
[1] has been selected in parameter 100
Configuration
, the maximum reference cannot be set
above parameter 414
Maximum feedback.
The
Maximum reference i
s ignored when the local
reference is active (parameter 203
Reference site).