A warning will flash in line 2, while an explanation is
given in line 1.
SETUP
1
WARNING 1
Under 10 V (10 VOLT LOW)
The 10 V voltage from terminal 50 on the control card
is below 10 V.
Remove some of the load from terminal 50, as the 10
Volts supply is overloaded. Max. 17 mA/min. 590
Ω
.
WARNING/ALARM 2
Live zero fault (LIVE ZERO ERROR)
The current or voltage signal on terminal 53, 54 or 60
is below 50% of the value preset in parameter 309,
312 and 315
Terminal, min. scaling.
WARNING/ALARM 4
Phase fault (MAINS PHASE LOSS)
Phase missing on the supply side.
Check the supply voltage to the VLT frequency
converter.
Alarm/warning limits:
VLT 6000 HVAC
3 x 200 - 240 V
3 x 380 - 460 V
[VDC]
[VDC]
Undervoltage
211
402
Voltage warning low
222
423
Voltage warning high
384
737
Overvoltage
425
765
The voltages stated are the intermediate circuit voltage of the VLT frequency converter with a tolerance
of ± 5 %. The corresponding mains voltage is the intermediate circuit voltage divided by 1,35.
■
■
■
■
■
Alarms
If an alarm is given, the present alarm number will be
shown in line 2. Lines 3 and 4 of the display will offer
an explanation.
WARNING 5
Voltage warning high
(DC LINK VOLTAGE HIGH)
The intermediate circuit voltage (DC) is higher than
Voltage warning high
, see table below. The controls of
the VLT frequency converter are still enabled.
WARNING 6
Voltage warning low (DC LINK VOLTAGE LOW)
The intermediate circuit voltage (DC) is lower than
Voltage warning low
, see table below. The controls of
the VLT frequency converter are still enabled.
WARNING/ALARM 7
Overvoltage (DC LINK OVERVOLT)
If the intermediate circuit voltage (DC) is higher than
the
Overvoltage limit
of the inverter (see table below),
the VLT frequency converter will trip after a fixed
period. The length of this period depends on the unit.
ALARM:12
SETUP
1
TRIP (RESET)
CURRENT LIMIT
WARN. 3
MAINS PHASE FAULT