VLT
®
6000 HVAC
44
MG.60.B1.02 - VLT is a registered Danfoss trade mark
■
■
■
■
■
General technical data
Cable lengths and cross-sections:
Max. motor cable length, screened/armoured cable ..................................................................................... 150 m
Max. motor cable length, unscreened/unarmoured cable ............................................................................. 300 m
Max. motor cable length, screened/armoured cable VLT 6011 380-460 V .................................................... 100 m
Max. DC-bus cable length, screened/armoured cable ............................ 25 m from frequency converter to DC bar.
Max. cable cross-section to motor, see next section
Max. cross-section for control cables ......................................................................................... 1.5 mm
2
/16 AWG
Max. cross-section for serial communication .............................................................................. 1.5 mm
2
/16 AWG
Control characteristics:
Frequency range ................................................................................................................................... 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ................................................................................................................................ 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
Speed, accuracy (open loop) ............................................................................. < 1500 rpm: max. error ± 7.5 rpm
> 1500 rpm: max. error of 0.5% of actual speed
Speed, accuracy (closed loop) ............................................................................ < 1500 rpm: max. error ± 1.5 rpm
> 1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of Display readout (parameters 009-012
Display readout)
:
Motor current [5], 0 - 140% load ............................................................ Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0 - 90% load .............................................. Max. error: ±5.0% of rated output power
Externals:
Enclosure ................................................................................................................................... IP 00, IP 20, IP 54
Vibration test ................................................................................................................................................... 0.7 g
Max. relative humidity ............................................................. 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
Ambient temperature IP 00/20/54 ............................................................ Max. 45°C (24-hour average max. 40°C)
Ambient temperature IP 20/54 VLT 6011 460 V ....................................... Max. 40°C (24-hour average max. 35°C)
Derating for high ambient temperature, see page 160
Min. ambient temperature in full operation ......................................................................................................... 0°C
Min. ambient temperature at reduced performance ....................................................................................... -10°C
Temperature during storage/transport ............................................................................................ -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
Derating for high air pressure, see page 160
EMC standards applied, Emission ............................................ EN 50081-1/2, EN 61800-3, EN 55011, EN 55014
Immunity .............................. EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4
EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
VLT 6000 HVAC protection:
•
•
•
•
•
Electronic motor thermal protection against overload.
•
•
•
•
•
Temperature monitoring of heat-sink ensures that the VLT frequency converter cuts out if the temperature
reaches 90°C for IP 00 and IP 20. For IP 54, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C.
•
•
•
•
•
The VLT frequency converter is protected against short-circuiting on motor terminals U, V, W.
•
•
•
•
•
The VLT frequency converter is protected against earth fault on motor terminals U, V, W.
•
•
•
•
•
Monitoring of the intermediate circuit voltage ensures that the VLT frequency converter cuts out if the
intermediate circuit voltage gets too high or too low.
•
•
•
•
•
If a motor phase is missing, the VLT frequency converter cuts out.
•
•
•
•
•
If there is a mains fault, the VLT frequency converter is able to carry out a controlled deramping.
•
•
•
•
•
If a mains phase is missing, the VLT frequency converter will cut out when a load is placed on the motor.